Explosion Isolation Valve None Return Valve
     
    Explosion isolation valve working principle
     
    The explosion isolation valve, is a passive one-way explosion-proof valve that is used on pipelines 
    containing combustible dust to allow dust and gas in the pipeline to pass through in one direction to 
    prevent the reverse propagation of the explosion. The correct use of explosion-proof valves can prevent 
    dust explosions from spreading from downstream pipelines to upstream pipelines, thereby effectively 
    avoiding "secondary explosions" or "multiple explosions", preventing the expansion of dust explosion 
    accidents, and protecting people and property Security. 
      This product is only used in negative pressure process system. Figure 2 is a schematic diagram of 
    negative pressure process system. The working principle of this product is shown in Figure 3. In normal 
    operation, the flap relies on the suction of the airflow in the pipe or manually opened to allow the gas 
    and dust in the pipe to pass through; the heavy hammer device is used to fix it in the fully opened 
    position. It not only prevents the wind speed in the pipeline from reducing the opening angle of the flap 
    to increase the wind resistance, but also prevents the flap from being completely closed and triggering 
    the locking device after the production is stopped. When a dust explosion occurs in the downstream 
    1container, the flap is quickly closed before the flame reaches under the dual action of the explosion 
    shock wave and the flap's gravity, and the locking device is triggered. Prevent the flap from reopening, 
    and prevent flames or sparks from spreading to the upstream pipeline of the explosion-proof flap valve.
        
    
     
    1. Bolts with a strength of not less than 8.8 should be used for installation. All bolts should be 
    tightened crosswise, symmetrically and evenly. After tightening, the bolts should show 2-3 
    pitches of the nut. Violent loading and unloading is strictly prohibited. 
    2. A sealing strip shall be provided between the explosion-proof flap valve and the flange connected 
    to the pipeline. 
    3. The strength of the pipeline between the explosion-proof flap valve and the protected container 
    should not be less than the maximum controlled explosion pressure of the explosion-proof flap 
    valve, namely pred, max. When the protected container adopts the explosion relief design, the10 
    maximum controlled explosion pressure That is the maximum explosion relief pressure. 
         
    4. The specifications of the explosion-proof valve should match the pipe diameter; if there is no 
    suitable specification, a specification that is only one size larger than the pipe diameter should 
    be selected. For example, the DN630 pipeline should use the DN650 explosion-proof valve. 
    5. The explosion-proof valve should be installed horizontally according to the indicated arrow on 
    the equipment, and the radial inclination angle should not exceed 10°. 
    6. The explosion-proof valve should be installed in the upstream direction of the protected 
    container (such as the dust collector), and the length of the pipeline between the protected 
    container and the protected container should meet the installation distance requirements of the 
    product. 
    7. The position of the counterweight has been adjusted to the correct position before the product 
    leaves the factory, and the position has been marked (the upper and lower positions of the 
    counterweight). The user must confirm that the counterweight is in the correct position before 
    installation: the upper and lower position marks are both exposed. If the counterweight is not in 
    the correct position, it must be adjusted to the correct position. At the same time, it is necessary 
    to confirm that the torque between the counterweight and the flap to the shaft is equal, that is, 
    the counterweight rod can stop at any position to maintain balance with the flap
     
    
    
    Use and maintenance requirements 
    1. Before starting the fan, check the position of the lock lever of the explosion-proof flap valve to 
    confirm that the lock lever is not locked. 
    2. Regularly check whether the bolts connecting the explosion-proof valve and the pipeline are 
    loose and fall off to ensure the overall sealing performance. The inspection period should not 
    exceed 6 months. 
    3. Regularly check the internal components of the explosion-proof valve to ensure that the 
    performance of the explosion-proof valve is complete, and the inspection period should not 
    exceed 6 months. 
    4. Regularly check whether the counterweight rod and shaft of the explosion-proof valve are tightly 
    fastened. The counterweight rod can be stopped at any position to maintain balance with the 
    flap. The inspection period should not exceed 6 months. 
    5. Regularly check whether the bearing is running smoothly and whether it is true. The inspection 
    period should not exceed 6 months. 
    6. This product is non-reusable and should be replaced immediately after explosion
     
    Specification
             
            
        
            
                